Absorption Chillers
What are Absorption Chillers?
Absorption chillers use a heat source to produce chilled water. Used heavily in industries where Chilled water is required, Absorption chillers are similar to refrigerators used in recreational vehicles.
World Energy
Goldman Energy source our Absorption Chillers from World Energy. As leaders in their field, World Energy’s Absorption Chillers are highly efficiency heat driven Chillers. They use heat sources such as hot water, exhaust gas, gas and oil firing and Steam.
Goldman Energy can supply a wide range of Absorption Chillers and Heat Pumps from World Energy that can be adapted to your specific needs.
World Energy has also supplied products to major players of fuel cell and Cogeneration system industry in Australia, America, Asia and Europe.
Goldman Energy Engineers:
- Size the Absorption chiller based on your consumption
- Source the Chiller from World Energy
- Install and Commission the Chiller into your plant
- Complete any ongoing maintenance required
Find out how Absorption Chiller work here
Chiller Selection
CHP Series
- Double Effect Exhaust Gas Driven Absorption Chiller
- Cooling Capacity: 176 - 7,032kW
- Chilled water inlet/outlet temp: 12/7oC
- Cooling water inlet/outlet temp: 32/37.2oC
- Heat source: Exhaust Gas
- Weight: 3.2 – 60+ tonnes
- COP: 1.2
HWAR LHH SERIES
- Single Effect Hot Water Driven Absorption Chiller
- Cooling Capacity: 105 – 4571KW
- Chilled water inlet/outlet temp: 13 / 8oC
- Cooling water inlet/outlet temp: 31 / 36.5oC
- Heat source: Hot Water
- Weight: 2.3 – 49 tonnes
- COP: 0.8 – 0.83
- Hot Water inlet/outlet Temperature 95 / 80oC
2AB Series
- Single Effect Double Lift Hot Water Driven Absorption Chiller
- Cooling Capacity: 105 – 4571KW
- Chilled water inlet/outlet temp: 13 / 8oC
- Cooling water inlet/outlet temp: 31 / 36.5oC
- Heat source: Hot Water
- Weight: 2.3 – 49 tonnes
- COP: 0.64 – 0.71
- Hot Water inlet/outlet Temperature 95 / 55oC
DW Series
- Double Effect Direct Fired Absorption Chiller and Heater
- Cooling Capacity: 176 – 5274KW
- Chilled water inlet/outlet temp: 12 / 7oC
- Cooling water inlet/outlet temp: 32 / 37.1oC
- Heat source: Direct fired
- Weight: 2.9 – 59 tonnes
- COP: 1 – 1.32
SW Series
- Double Effect Steam Fired Absorption Chiller
- Cooling Capacity: 176 – 5274KW
- Chilled water inlet/outlet temp: 12 / 7oC
- Cooling water inlet/outlet temp: 32 / 37.1oC
- Heat source: Steam
- Weight: 4.4 – 45.3 tonnes
- COP: 0.81 – 1.48
Qantas Trigeneration Project
- Automation and Control
- Absorption Chillers
- Cogeneration
- Install and Commission
- Maintenance
- Trigeneration
- Onicon
- Turnkey Solution
- System Design
- Remote Control
- ComAp
- Cogeneration and Trigeneration
We were approached to provide Trigeneration facilities for the Qantas jet base facility in Mascot, NSW. We designed, installed, commissioned, and maintained, the plant. Throughout 2014 Goldman...
Read More...Ausgrid Learning Centre Trigeneration
- Automation and Control
- Absorption Chillers
- Cogeneration
- Install and Commission
- Maintenance
- Trigeneration
- System Design
- Remote Control
- Turnkey Solution
- ComAp
The new Energy Australia Learning Centre will be the country’s largest electrical learning centre and will be home to the next generation of front line...
Read More...- 1/10 Anella Avenue, Castle Hill NSW 2154
- Contact Us